| Function | Ring main unit nuclear phase and frequency, phase, phase sequence test | 
| power supply | Host: 3.7V, 2600mAh rechargeable lithium battery Detector: 3.7V, 600mAh rechargeable lithium battery | 
| Nuclear phase voltage | AC 1V~600V | 
| nuclear phase distance | 30m | 
| Differential characterization | In-phase: -20°~20°; Out-of-phase: 100°~140° and 220°~260° | 
| range | Test phase: 0°~360° | 
| Test frequency: 45.0Hz~65.0Hz | 
| Accuracy | Phase: ≤±8° | 
| Frequency: ≤±2Hz | 
| Resolution | Phase: 1° Frequency: 0.1Hz | 
| transmit frequency | 433MHz, 315MHz | 
| LCD size | 3.5-inch color screen; display area: 71mm×53mm | 
| Phase indication | Simultaneous display of vector graphics and numbers | 
| Display rate | 2 times/sec | 
| data storage | 200 groups (power failure will not lose data) | 
| Automatic shut-down | After about 15 minutes of power on, the meter will automatically shut down | 
| battery voltage | The host battery has a 4-grid power display. When there is only 1 grid or 0 grid, please charge it; when the indicator light of the detector flashes rapidly, it means that the battery voltage is low, please charge. | 
| Rated current | Detector: 30mA max; Host: 150mA max | 
| Instrument quality | Instrument: about 750g (including battery) | 
| Instrument size | Host 195mm×100mm×45mm; Detector 120mm×54mm×30mm | 
| Insulation test | Host and detector: AC3700V/rms (between exposed metal and plastic casing) | 
| outside interference | No strong electromagnetic field; no 433MHz, 315MHz co-channel interference | 
| Working temperature and humidity | -10℃~40℃; below 80%rh | 
| Storage temperature and humidity | -10℃~60℃; below 70%rh | 
| Protection class | IP63 | 
| Suitable for safety regulations | GB13398-92, GB311.1-311.6-8, 3DL408-91 standards and the newly promulgated national power industry standard "General technical conditions for 1kV ~ 35kV portable nuclear phase detectors for live work DL/T 971-2017" requirements | 
| Comply with IEC61481-A2; 2004; IEC 61243-1 ed.2:2003 standard |