MEWOI8005E 10KV/12KV Dielectric loss tester,capacitance dissipation factor tester,Transformer Capacitance&Tan Delta Dissipation Factor Tester

Tan Delta Tester

  • Main Features:: Dielectric loss Measurement
  • Model No.:: MEWOI8005E
  • Name:: MEWOI8005E Dielectric loss tester


Contact Us for QuotationEmail:mewoi@mewoi.comWhatsapp: +8618620373879

INTRODUCTION

Dielectric loss measurement is a basic method in insulation test and effectively detect damp, degradation and partial defect of insulation of electrical equipment. This method is widely used in electric manufacturing, electric equipment installation, connection and preventive test. Measurement on dielectric loss of transformer, mutual inductor, reactor, capacitor, bushing and arrester is the most basic method to test their insulation property.TKC fully-automatic anti-interference dielectric loss tester breaks through the traditional bridge testing method and adopts variable frequency power technology, single chip and modernized electrical technology to carry out automatic frequency shift, analog-to-digital conversion and data computing. It features strong anti-interference capacity, high test speed, high precision, automatic digitization and easy operation. It adopts high-power switching power supply, which outputs 45Hz and 55Hz pure sine wave and automatically increase the voltage to a maximum value 10 KV. It can filter 50Hz interference automatically, and it is applicable to the site test of substation and other places with large electromagnetic interference. This methods is extensively applied in dielectric loss measurement of transformer, mutual inductor, reactor, bushing, capacitor, arrester and other equipments in power industry

PERFORMANCE FEATURES

1. The instrument adopts complex number current method to measure capacitance, dielectric loss and other parameters. The measured result is highly accurate and it is easy to realize automatic measurement. 

2. The instrument adopts variable frequency technology to eliminate 50Hz/60Hz power frequency interference. So a reliable data will be reachable even under the strong electromagnetic interference.

3. The instrument adopts large screen LCD . In the process of testing, Chinese menu prompt is visualized and easy to operate.

4. The instrument is easy to operate and the measuring process is controlled by microprocessor. Once a suitable measuring method is selected, the data measurement will complete automatically under the control of microprocessor.

5. The instrument is designed to be an integrated model with reference capacitor and HV power supply in it, enables site test measurement and reduces site wiring.

6. The instrument is equipped with CVT testing function, which can achieve CVT self-exciting testing without external accessories and measure the capacitance and dielectric loss of C1 and C2 by at a time.

7. GST measurement adopts ivddv technology and avoids unstable data provided by previous GST measurement.

8. The instrument provides low voltage shell function of GST. When the bus of 220kV CVT is grounded, dielectric loss measurement can be conducted for C11 without removing 10 kV GST.

9. The instrument has a function of measuring high-voltage dielectric loss. It can carry out dielectric loss test with over 10kV with the help of voltage transformer or series resonance.

10. The instrument has a ground-fault protection function. In case that the instrument is not grounded or grounded incorrectly, the instrument will refuse to enter in o normal procedure and output HV. As for the over-current protection function, it will protect the instrument from damage when the tested article is in a short circuit or breakdowns.

11. The instrument has a function of electric shock protection. When the instrument operator suffers an electric shock due to incaution, the instrument will cut off the HV immediately and thus ensure the security of operator

TECHNICAL SPECIFICATION


Accuracy

Cx:        ±(reading×1%+1pF)

tgδ

±(reading×1%+0.00040)

Anti-interference

Variable frequency anti-interference, the above accuracy can be reached under 200% interference.

Capacitance range

Internal HV:      3pF~60000pF/12kV        60pF~1μF/0.5Kv

External HV: 3pF~1.5μF/10kV        60pF~30μF/0.5kV

Resolution: Maximum 0.001pF, 4 valid figures.

tgδ range

Unlimited, 0.001% resolution, automatic identification for capacitance, inductance and resistance of three tested articles.

Test current range

10μA~5A

Internal HV

Set voltage range: 0.5~12kV

Maximum output current: 200mA

Buck-bust method: continuous stepless regulation

Test frequency: 45, 50, 55 single frequency

45/55Hz automatic dual variable frequency

Frequency accuracy: ±0.01Hz

External HV

In case of UST, maximum test current is 1A, and power frequency or variable frequency is 40-70Hz

In case of GST, maximum test current is 10kV/1A, and power frequency or variable frequency is 40-70Hz

CVT self-exciting low voltage output

Output voltage 3~50V,

output current 3~30A

Measuring duration

About 40s, depending on measuring method

Input power supply

180V~270VAC, 50Hz/60Hz±1%, supplied by alternating current or generator

Computer interface

Standard RS232 interface

Printer

WH-A7 mini-type thermal printer

Environment temperature

-10℃~50℃

Relative humidity

<90%

Overall dimension

460×360×350mm

Weight

28kg

Note:

On-site transformer housing is generally grounded. When testing the tgδ(dielectric loss) of transformer, the reverse connection method is generally selected. Only for fully insulated transformer, the forward connection method is used to test.

1F=1000mF=1000000000uF=1000000000000pF

1mF=100001F=1000uF=1000000000000pF

1uF=1000000000000pF

1uF=0.000001F