MEWOI4600 Intelligent Equipotential Bonding Resistance Tester

The main function Equipotential bonding resistance between metal components, resistance of connecting conductors between ground grids and ground electrodes, and measurement of contact low resistance resistance. Range: 0.0010Ω~40Ω Maximum test current: 1A Data storage: 6000 groups Alarm function: sound and light alarm

  • Model No.:: MEWOI4600
  • Name:: MEWOI4600 Intelligent Equipotential Bonding Resistance Tester
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Product introduction

MEWOI4600 Intelligent Equipotential Bonding Resistance Tester is used to measure the resistance of connecting conductors between various electrical equipment and the earth grid and the equipotential resistance between metal components in buildings. It can also measure the contact resistance of switches and socket contacts. And other low-value resistors , with micro-ohm meter function, range: 0.0010Ω~40Ω .

MEWOI4600 intelligent equipotential bonding resistance tester consists of a host, monitoring software, test lines, communication lines, etc. Host LCD display, Chinese operation interface, clear at a glance. At the same time, it has a large storage space and can store 6000 sets of data. The monitoring software has online real-time monitoring and historical query functions, dynamic display, maximum, minimum, average value indication, alarm value setting and alarm indication functions, and historical data reading, consulting, saving, reporting, printing and other functions.

Technical parameter

power supply  DC7.4V 2.6Ah rechargeable lithium battery
LCD size  44mm×27mm (with backlight)
Range  0.0010Ω~40Ω
Resolution  Resistance: 0.0001Ω
precision  0.1Ω~40Ω, △≤1% Rx (Rx is the measured resistance value)
  0.01Ω~0.1Ω,△≤10%·Rx
data storage  6000 groups
Data upload function  With RS232 interface, software monitoring, stored data can be uploaded to computer, saved and printed
Automatic shut-down  no automatic shutdown
power  Working current: 1A Max
working environment  -10℃~40℃; below 80%rh
storage environment  -10℃~60℃; below 70%rh
Measurement methods  2-way A/D simultaneous detection
measure time  3 seconds/time
line voltage  try to avoid
overflow display  "OL" symbol display
Alarm function  When the measured value exceeds the alarm setting value, "beep-beep-beep--" alarm prompt
low battery  When the battery voltage drops to about 5V, the low battery voltage symbol will be displayed to remind you to replace the battery.
overload protection  Ground resistance: AC 280V/3 seconds between each port of EP and EC
Insulation resistance  More than 20MΩ (500V between the circuit and the shell)
Pressure resistance  AC 3700V/rms (between the circuit and the case)
Electromagnetic properties  IEC61010-4-3, radio frequency electromagnetic field≤1V/m
Suitable for safety regulations  IEC61010-1 (CAT Ⅲ 300V, CAT IV 150V, pollution degree 2);
  IEC61010-031;
  IEC61557-1 (grounding resistance);
  IEC61557-5 (soil resistivity);
  JJG 366-2004。
Clamp quality  About 1300g (including battery)
Meter size  Length x width x thickness: 205mm x 200mm x 85mm


Product number

modelMaximum test currentRangehighest resolution
MEWOI46001A0.0010Ω~40Ω0.0001Ω
MEWOI47002a1mΩ~30.0kΩ1mΩ
MEWOI4700C4A1mΩ~30.0kΩ1mΩ


Telephone
E-mail
After Sales
QQ